Model
|
Hipulse E
|
|
Power
|
400Kva
|
|
320Kw
|
|
System efficiency
|
|
AC-AC online double conversion
|
up to 96%
|
|
Input Parameters
|
|
nput Voltage to Rectifier
|
380/400/415VAC, three-phase four-wire
|
|
Input Voltage to Bypass
|
380/400/415*(400V:nominal) 3-phase +N, 4-wire
|
|
Permissible Input Voltage Range
|
323 to 457
|
|
input Frequency
|
40Hz - 70Hz
|
|
Permissible Input Frequency Range
|
47Hz or 63Hz
|
|
Input THDi at nominal voltage at full load
|
<4%-5% with 12-pulse + Filter
|
|
Input Power Factor at nominal voltage
|
>=0,90% with 12-pulse + Filter
|
|
Flexi Power Walk-In
|
5 to 120 (selectable) second
|
|
Battery & DC Parameters
|
|
Battery Type
|
VRLA (Valve Regulated lead Acid) or Wet or NiCd
|
|
Nominal Battery Bus
|
396 (Float Voltage: 446V)
|
|
End-Cell Voltage
|
Selectable from 1,65 to 1,90 (for VRLA/Wet Cells)
|
|
DC ripple voltage in float & Const V Ch.mode
|
<1 (RMS value)
|
|
Temperature compensated Battery Charging
|
Optional
|
|
Output Parameter
|
|
inverter output
|
IGBT-based Sine-Sine PWM Cotrolled
|
|
Output Power
|
??kw
|
|
Output Voltage
|
380/400/415* (400V:nominal) 3-phase, 4-w
|
|
Output Voltage Regulation
|
* +/- 0,5 (3 phase RMS average)
|
|
Output Frequency
|
50Hz or 60Hz
|
|
Output Frequency Regulation
|
%+/- 0,05
|
|
Output Voltage THD at nominal voltage
|
1 (typ), 2% (max)
|
|
Capability to handle High Crest Factor Load
|
3:1 (compliant with IEC 62040-3)
|
|
Capability to handle Step Load
|
0-100 or 100-0
|
|
Transient Recovery
|
Msecond 10 (recovery to 95% of the voltage level)
|
|
Capability to handle Leading PF Load
|
Up to 0,7**
|
|
Voltage Displacement
|
120° +/- 1° el (with 100% unbalanced load)
|
|
Overload Conditions
|
110 for 60 minutes
125 for 10 minutes
150 for 1 minutes
|
|
System Parameters
|
|
UPS Efficiency (without any power option)
|
Up to 93,5 (depends on rating & operating condition
|
|
Physical Parameters & Standards
|
|
Width (applicable to 12 pulse version)***
|
1250mm
|
|
Depth
|
850 mm
|
|
Height
|
1900 mm
|
|
Weight 12p (approx.)
|
1400 kg
|
|
Colour
|
Ral 7035
|
|
Front door Opening (for better Serviceability)
|
IP 20 even with front door in opened condition
|
|
Standards & Conformities
|
IEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE Mark ;
EN 62040-1-1,
EN 50091-2, EN62040-3, EN 60950, EN 60529 and VFI 111
|
|
Enviromental Parameters
|
|
Operating temperature range
|
0 - 40°C *
|
|
Storage temperature
|
25 ,70°C
|
|
Maximum operating altitude
|
≤1000m, When operating at 1000>2000m, derated by 1%
for every 100m increase of altitude
|
|
Relative Humidity
|
≤95%
|
|
Noise (1m)
|
55-62dB, adjusted according to load rate
|
|
IP Class
|
IP20
|
|
Standards
|
Safety: IEC60950-1; IEC62040-1-1/AS62040-1-1
EMC: IEC62040-2/AS62040-2/EN50091-2 CLASS A
Design and test: IEC62040-3/AS62040-3
|