Models
|
Nxe
|
|
Rated Power @ 0.8 PF [kVA]
|
10Kva
|
|
Rectifier Input
|
|
Rectifier Type
|
IGBT-based Vector Controlled PFC (PF Corrected)
|
|
Input Voltage [Vac]
|
380 / 400 / 415 (Accepted from 305 to 477 without batt. Use)
|
|
Input Frequency [Hz]
|
50 or 60 (Accepted range from 40 to 70)
|
|
Input Current
|
THD <3% (without any Filter)
|
|
Input Power Factor
|
≥ 0.99 (without any Filter)
|
|
Power Walk-In [s]
|
5 to 30 (selectable)
|
|
Bypass Input
|
|
Input Voltage [Vac]
|
380 / 400 / 415
|
|
Battery
|
|
Battery Type
|
VRLA (Valve Regulated Lead Acid) or Wet / Flooded or NiCd
|
|
End-Cell Voltage [Vdc/Cell]
|
Selectable from 1.60 to 1.90 (for VRLA)
|
|
DC Ripple Current (float)
|
<5% (of C10 AH capacity) RMS value
|
|
DC Ripple Voltage
(float & const V Ch)
|
<1% (RMS value)
|
|
Temp. Comp. Charge
|
Standard (where internal batteries 10, 15, 20, 30, 40 kVA)
and Optional (for all other battery configurations)
|
|
Output
|
|
Inverter Type
|
IGBT-based Vector, Repetitive & PI Controlled
|
|
Output Power [kW]
|
8Kw
|
|
Output Voltage [Vac]
|
380 / 400 / 415 +/- 0.5 Regulation (3-phase RMS average)
|
|
Output Frequency [Hz]
|
50 or 60 with +/- 0.05 Regulation
|
|
Output Voltage THD
|
1% (max)
|
|
Max. Load Crest Factor
|
3:1 (compliant with IEC 62040-3)
|
|
Transient Volt. Resp. [ms]
|
10 to recover ± 5% of Nominal Voltage for 0% to 100% or 100% to 0% step load
|
|
Max. Leading PF Load
|
Up to 0.9
|
|
Voltage Displacement [°el]
|
120°+/-10 el (with 100% unbalanced load)
|
|
Overload
|
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute
|
|
Efficiency
|
|
AC-AC
|
Up to 96
|
|
Physical Parameters
|
|
Width [mm]
|
600
|
|
Depth [mm]
|
700
|
|
Height [mm]
|
1400
|
|
Weight (approx.)
|
|
without batt. [kg]
|
180
|
|
UPS Enclosure IP
|
IP 20 (even with open front door)
|
|
Standards
|
IEC 62040-3, IEC 62040-2, IEC 62040-1-1, IEC 60146-1-1,
IEC 61000-4-2, 4, 5, 6, 8,11, EN 50091-1-1, EN 50091-2,
EN 50091-3, EN 60950, EN 60529, ANSI C62.41 (IEEE 587)
|
|
EMC Class
|
Class-A (Applicable for both Radiated & Conducted)
|
|
Environmental
|
|
Storage Temp. [°C]
|
*-20 to 70 (UPS) & -20 to 30 (Battery)
|
|
Operating Temp. [°C]
|
0 to 40 (UPS) & 25 +/-5 (Battery)
|
|
Relative Humidity
|
0 to 95% (non-condensing)
|
|
Maximum Altitude [m]
above Mean Sea Level
|
1000 (as per IEC 62040/3)
|